| Use power | AC100V ± 10V 50 / 60Hz | 
        
            | Power capacity | Up to about 600VA | 
        
            | Output current | AC0 ~ 0.5 / 5 / 40A (15 seconds rating) | 
        
            | Output capacity | AC40A output during 600VA | 
        
            | ammeter | 0.5 / 5/50 (Class 1.5 True RMS conversion method) | 
        
            | counter | 0 ~ 199.999sec resolution 1Ms 200 ~ 1999.99Sec resolution 10Ms
 (with automatic carry function)
 | 
        
            | Counter accuracy | 0.01 Pasento rdg ± ± ± 1Dgt 5Ms ± ⊿T ⊿T: each error of the stop signal
 contacts, DC voltage 1Ms ±
 AC voltage (5 ~ 10V) ± 5Ms
 AC voltage (10 ~ 20V) ± 2.5Ms
 AC voltage (more than 20V) ± 1ms
 self-power ± 3ms
 case of ※ stop due to self-supply, depends on the supply load state of the power supply (back electromotive force due to the rotation device, etc., the residual voltage of the capacitor, etc.). The above accuracy, power supply of the counter is the accuracy of to completely cut off.
 | 
        
            | Stop signal | Contact: a contact, b contact automatic detection voltage: direct current, alternating current with 10 ~ 220V applied, remove
 the self-power: the display time for about 5 minutes
 there is no power at the same time tester (the relay is operated, it is that the counter is stopped. )
 * with automatic reset function
 | 
        
            | Auxiliary power | AC100V ± 10V 5A | 
        
            | External dimensions | 196 (D) × 296 (W) × 215 (H) | 
        
            | weight | About 9kg | 
        
            | accessories | Test code set (with storage bag) instruction manual |