| Use power | AC100V ± 10V 50 / 60Hz | 
        
            | Output voltage | Variable output: AC0 ~ 130V constant current output: AC50V ± 5V | 
        
            | Withstand voltage output current | 15A (30 minute rating) * overcurrent protection circuit will operate at about 16.5A. | 
        
            | Relay output current | Variable Output: AC50A (30 seconds rated) constant current output: The output Zerokusu output.
 | 
        
            | Current range | Adjustable Output: AC0.1 / 0.25 / 0.5 / 1 / 2.5 / 5/10/25 / 50A constant current output: AC3 / 3.5 / 4 / 4.5 / 5A relay tap for 150/200/300/400/500/700 / 1000% of the current output
 * output current for each set value, displayed on the display.
 | 
        
            | Output frequency | The same as the input power source | 
        
            | Total distortion factor | Variable output: the same as the input power supply constant current output: within 10%
 | 
        
            | Output stability | Variable output: the same as the input power supply constant current output: within ± 1% of each range
 | 
        
            | Indicating instrument | 0.1 / 0.25 / 1 / 2.5 / 5/10/25 / 50A moving coil-shaped, 1.0 grade with mirror (True RMS conversion method)
 | 
        
            | counter | 0 ~ 199.999sec resolution 1Ms 200 ~ 1999.99Sec resolution 10ms (with automatic carry function)
 | 
        
            | Counter accuracy | 0.01 Pasento rdg ± ± ± 1Dgt 5Ms ± ⊿T ⊿T: each error of the stop signal
 contacts, DC voltage 1Ms ±
 AC voltage (5 ~ 10V) ± 5Ms
 AC voltage (10 ~ 20V) ± 2.5Ms
 AC voltage (more than 20V) ± 1ms
 self-power ± 3ms
 case of ※ stop due to self-supply, supply load state of the power supply (by the rotating equipment, etc.
 depends on the counter-electromotive force, the residual voltage of the capacitor, etc.).
 The above accuracy, power supply of the counter is the accuracy of to completely cut off.
 | 
        
            | Stop signal | Contact: a contact, b contact automatic detection voltage: direct current, alternating current with 10 ~ 220V applied, remove
 the self-power: there is no power at the same time tester and the display time for about 5 minutes (the relay is operated, it is that the counter is stopped. )
 * count start from 600 seconds (10 minutes from the start) at the time that elapsed, the operation buzzer, the operation lamp will operate for 10 seconds.(Timer function for pressure test)
 * with automatic reset function
 | 
        
            | Auxiliary power | AC100V (outputs the input power) 10A | 
        
            | External dimensions | 300 (D) × 500 (W) (excluding protrusions) × 200 (H) | 
        
            | weight | About 18kg | 
        
            | accessories | Test code set (with storage bag) owner manual case cover |