| Use power | AC100V ± 10% 50Hz / 60Hz | 
        
            | Auxiliary power | AC100V 5A power input to output. Non-insulated from the power input
 | 
        
            | Zero-phase voltage output | range | AC30 / 300 / 1000V (resolution 0.1 / 1 / 1V) | 
        
            | capacity | 15VA 30-minute rating | 
        
            | Display instrument | 3 digit 1/2 LCD display | 
        
            | Sampling rate | 50Hz: 6.25 times / sec 60Hz: 7.5 times / sec.
 | 
        
            | accuracy | ± 1% rdg ± 5dgt (30V range is ± 1% rdg ± 10dgt) | 
        
            | Zero-phase current output | range | AC1 / 2.5A (resolution 0.001 / 0.01A) | 
        
            | capacity | 2.5A maximum load impedance 1Ω 30-minute rating | 
        
            | Display instrument | 3 digit 1/2 LCD display | 
        
            | Sampling rate | 50Hz: 6.25 times / sec. | 
        
            | accuracy | ± 1% rdg ± 5dgt | 
        
            | phase | Adjustable range | LEAD180 ° ~ 0 ~ LAG180 ° | 
        
            | Display instrument | LCD Display resolution 1 ° | 
        
            | accuracy | ± 3 ° | 
        
            | counter | Measurement range | 0 ~ 199.999sec resolution 1Ms 200 ~ 1999.99Sec resolution 10ms automatic carry
 | 
        
            | Stop signal | Contact a contact point b-contact automatic detection | 
        
            | Voltage direct current is applied, removed both about 25 ~ 220V AC application about 20 ~ 220V
 removed about 50 ~ 220V
 | 
        
            | Self-powered display time for about 5 minutes | 
        
            | accuracy | 0.01 Pasento rdg ± ± ± 1Dgt 5Ms ± ⊿T ⊿T: each of the stop signal error
 | 
        
            | Inertia output | 50ms fixed | 
        
            | External dimensions | 193 (D) × 308 (W) × 260 (H) | 
        
            | weight | 7kg | 
        
            | accessories | Test code set (with storage bag) Operating Instructions |