Reference cond.: |
Per EN 60770-1
TU = konst. (15…25) °C
φ = konst. (45...75) % r.F.
pU = konst. (860...1060) mbar
UB = 24 V DC (± 3 V DC)
RB = 50 Ω, HART: 250 Ω
Ground connected
MBA = 0 bar |
Calibration position: |
Process connection bottom: vertical |
Deviation of characteristic: |
Refer to the adjusted measuring span (Limit point method per DIN 16086) |
|
Nominal range 1-16 bar:
Turndown 5:1 0.1 %
Turndown > 5:1 0.02 % x TD |
|
Nominal range 0.25 bar:
Turndown 5:1 0.15 %
Turndown > 5:1 0.03 % x TD |
Long-term drift: |
Refer to nominal range ≤ 0.1 %/year |
Operational availability: |
< 12 s |
Response time t90 at current output |
for 20 Hz measuring rate: typically 120 ms
for 100 Hz measuring rate: typically 50 ms |
Temperature influence, case: |
Refer to nominal range |
|
Ambient temperature -20…80 °C:
Nominal range 1-16 bar, 0.1 %/10K, max. 0.3 %
Nominal range 0.25 bar, 0.15 %/10K, max. 0.4 % |
|
Ambient temperature -40…-20 °C:
Typical 0.2 %/10K |
Temperature influence, process connection: |
The temperature influence depends on several parameters, e.g. diaphragm di-ameter, diaphragm material, capillary length, capillary diameter, systeme filling, etc.
We provide a detailed error analysis upon request. |
Influence static pressure: |
Refer to nominal range |
|
0.25 bar 0.12 % x stat. pressure [bar] x TD
1 bar 0.03 % x stat. pressure [bar] x TD
4 bar 0.02 % x stat. pressure [bar] x TD
16 bar 0.005 % x stat. pressure [bar] x TD
40 bar 0.004 % x stat. pressure [bar] x TD |