Reference cond.: |
per DIN EN 60770-1 |
|
TU = const. (15…25) °C
φ = const. (45...75) % r.F.
pU = const. (860...1060) mbar
UB = 24 V DC (± 3 V DC)
RB = 50 Ω, HART: 250 Ω
Ground connected
MBA = 0 bar |
Calibration position: |
Vertical mounting position, bottom connection |
Deviation of characteristic: |
Refer to the adjusted measuring span (Limit point method per DIN 16086) |
|
Nominal range 1-400 bar, 1-16 bar abs.: |
|
Turndown 5:1 0.1 %
Turndown > 5:1 0.02 % x TD |
|
Nominal range 0.25 bar: |
|
Turndown 5:1 0.2 %
Turndown > 5:1 0.04 % x TD |
Long-term drift: |
Refer to nominal range ≤ 0.1 %/year |
Operational availability: |
< 12 s |
Response time t90 at current output: |
Refer to nominal range |
Temperature influence, case: |
Ambient temperature -20…80 C: |
|
Nominal range 1-400 bar
0.1 % /10K, max. 0.3 % |
|
Nominal range 0.25 bar
0.15 % /10K, max. 0.4 % |
|
Ambient temperature -40…-20 C: |
|
Typical 0.2 % /10K |