RI-215A |
RI-215D |
Detection Method
|
Non dispersive infrared absorption method (NDIR)
|
Sample Method
|
Diffusion
|
Sample drawing pump
|
Measuring Gas
|
Carbon dioxide (CO2) in air
|
Measuring Range
|
0-2,000ppm, 0-5,000ppm, or 0-9,990ppm * Specify one of these ranges when ordering
|
Resolution
|
1 ppm for 0-2,000 ppm
10 ppm for 2,000-9,990 ppm
|
Repeatability
|
± 3% of full scale (at constant temperature and humidity conditions)
|
Output Signal
|
0-10VDC linear (load resistance: Min. 300K ), or 4-20mADC linear (load resistance: Max. 500 )
*Specify one of these outputs when ordering
|
Flow Rate
|
N/A
|
Above 1.0 liter/min
|
Alarm Range
|
50 ppm - Full scale (adjustable in steps of 10 ppm)
*Standard alarm point 1,000 ppm
|
Alarm
|
125VAC, 0.5A (load resistance), Dry contact (normally open)
|
Operation Temp. & Humidity
|
0 ~ 40ºC (32-104ºF), 10-90%RH (non-condensing)
|
Warming Up Time
|
30 minutes for full warm up (display starts after 1 minute)
|
Power Requirement
|
24 VDC ± 10% or 24 VAC ± 10%
|
115 VAC or 220 VAC, ± 10%, 50/60 Hz
|
Installation Method
|
Wall mount vertically, indoor locations only
|
Outer Dimensions
|
Approx 78(W) x 78(H) x 31(D) mm
Approx 3.1(W) x 3.1(H) x 1.2(D) in. |
XApprox 220(W) x 200(H) x 76(D) mm
Approx 8.7(W) x 7.9(H) x 3.0(D) in.
|
Weight
|
Approx. 200g (6.50 oz.) |
Approx. 3.6kg (7.9 lbs.) |