Humidity Meters - Gas Selection 907021 JUMO

Mã sản phẩm: 907021 |
Thương hiệu: Jumo

Giá bán: Liên hệ
Features


Available in the indoor, wall-mounted, and duct version
Miniature rod version for OEM applications
With current or voltage outputs as well as passive temperature output
Hygro thermometer as tabletop/wall-mounted indicator

Yêu Cầu Giá Tốt

Thông tin sản phẩm

Specification: 

Humidity sensor Capacitive, can take condensation (with sensor coating)
Humidity measuring range 0 to 100 % RH
Humidity working range 10 to 90 % RH: Tabletop and wall-mounted indicator, indoor version
10 to 95 % RH: Wall-mounted and duct version (HVAC)
0 to 100 % RH: Wall-mounted and duct version, rod version
Humidity accuracy at 20 °C ±2 % RH:    Indoor version and display unit in the humidity range of 40 to 60 % RH,
                  wall-mounted and duct version in the humidity range of 0 to 90 % RH,
                  rod version with Modbus output, (in the remaining range ±3 % RH)
±2.5 % RH: Wall-mounted and duct version (HVAC),
                   rod version (for DC 24 V, 20 °C and 0.2 m/s)
±3 % RH:    Indoor version with CO2 in the humidity range of 30 to 70 % RH,
                  (in the remaining range ±5 % RH)
Temperature dependency ±0.03 % RH/°C (typical)
Sensor coating Sensor coating for the humidity sensor is an additional protective coating, which offers better protection from contaminants for the humidity sensor and in many cases allows for longer service life, especially with particularly contaminated or aggressive atmospheres. With the exception of the indoor version, all devices are equipped with this feature for increased protection as standard.

Temperature (T) 
Temperature sensor Platinum-chip temperature sensor Pt1000 according to DIN EN 60751, (passive also Pt100)
Temperature measuring range 0 to 50 °C:       Indoor version; wall-mounted and duct version (HVAC) and (CO2)
-5 to +55 °C:   Tabletop and wall-mounted indicator
-40 to +80 °C: Wall-mounted and duct version (observe admissible ambient temperature)
-40 to +60 °C: Rod version (-40 to +80 °C with Modbus output)
Temperature accuracy at 20 °C ±0.2 °C:         Wall-mounted and duct version, rod version with Modbus output (±0.6 °C in the end range at 20 °C)
±0.3 °C:         Indoor version – voltage output, duct version (CO2)
±0.4 °C:         Indoor version – current output (±0.7 °C with CO2)
±0.3 °C:         Wall-mounted and duct version (HVAC); rod version, tabletop and wall-mounted indicator

Carbon dioxide (CO2)
Measuring principle NDIR (non-dispersive infrared technology)
Sensor 2-beam infrared cells
Measuring range 0 to 2000 ppm, 0 to 5000 ppm
0 to 10000 ppm (only wall-mounted and duct version)
Accuracy at 25 °C and 1013 mbar ±(50 ppm +2 % of the measured value) for 0 to 2000 ppm
±(50 ppm +3 % of the measured value) for 0 to 5000 ppm
±(100 ppm +5 % of the measured value) for 0 to 10000 ppm
Temperature dependency 2 ppm CO2/°C (typical)
Long-term stability 20 ppm/a (typical)
Sampling rate Approx. 15 s
Response time < 195 s (300 s for wall-mounted version)
Warm-up time < 5 min

Electrical data
Voltage supply 2× DC 1.5 V alkaline batteries:   Tabletop and wall-mounted indicator
DC 15 to 35 V, AC 24 V ±20 %:  For output of 0 to 10 V / RS485 or CO2 measuring probe
DC 20 to 28 V:                          For output of 4 to 20 mA
DC 20 to 35 V:                          For output of 4 to 20 mA (HVAC)
DC 4.5 to 30 V:                         Only rod version with voltage output
DC 9 to 28 V:                            Only rod version with current output
DC 4 to 18 V:                            Only rod version with Modbus output
Current consumption 5 to 15 mA for DC voltage supply (wall-mounted and duct version)
13 to 25 mA for AC voltage supply (wall-mounted and duct version)
1.5 mA for rod version (typical 0.4 mA for Modbus output, sampling rate 1 s)
10 mA plus output current, max. 0.5 A for 0.3 s for CO2 measuring probe
Load resistance RL < 500 ohm with current output
Output signals 4 to 20 mA and 0 to 1 V, 0 to 10 V, passive also Pt100 and Pt1000
RS485 digital output
Electromagnetic compatibility EN 61326-1 and EN 61326-2-3
Connection Screw terminals max. 1.5 mm2
Connection diagram See operating manual

Case
Case Polycarbonate
Protection type IP20: indoor version, tabletop and wall-mounted indicator
IP65: wall-mounted, duct and rod version
Cable entry M16 × 1.5 wall-mounted and duct version
Ambient temperature -20 to +60 °C:   Indoor version, wall-mounted and duct version (CO2)
-5 to +55 °C:     Indoor version with LCD display, tabletop and wall-mounted indicator
-15 to +60 °C:   Wall-mounted and duct version (HVAC)
-40 to +60 °C:   Wall-mounted and duct version (-20 to +50 °C with LCD display)
-40 to +60 °C:   Rod version
Storage temperature -20 to +60 °C:   Indoor version
-25 to +60 °C    Wall-mounted and duct version (HVAC)
-40 to +60 °C    Wall-mounted, duct and rod version
Weight Approx. 100 g:  Indoor version and tabletop and wall-mounted indicator
Approx. 150 g:  Wall-mounted version
Approx. 250 g:  Duct version
Approx. 150 g:  Rod version (1.5 m connecting cable, standard)
Approx. 180 g:  Rod version (3 m connecting cable)