Operating Conditions |
Measurement medium |
Water or other conductive liquids
Minimum conductivity:20 μS/cm |
Medium temperature |
In combination with a PVC fitting: 0 to +50°C
In combination with a PE fitting: 0 to +70°C
In combination with a PP fitting: 0 to +80°C
In combination with a stainless steel fitting:-15 to +150°C |
Ambient temperature |
-10 to +60°C operating temperature
-20 to +60°C storage temperature |
Tube diameter |
For diameters DN15 to DN 400.
Only in combination with fittings as per Data Sheet 406090. |
System pressure |
In combination with a PVC or PE fitting:
|
Minimum inlet and
outlet distances |
See illustrations on page 5/5 |
Relative humidity |
< 80%, non-condensing |
Enclosure protection |
IP65 |
EMC |
EN 50081-1, EN 61000-6-2 |
Safety |
EN 61010-1 |
Vibration |
EN 60068-2-6 |
Impact |
EN 60068-2-27 |
Measuring range |
Flow speed |
0.2 to 10 m/s |
Accuracy
(With a flow speed
of from 1 to 10 m/s
and a medium
temperature in the range
from -15 to 70°C) |
With standard K factor: ≤ ± 4% of measured value
After teach-in: ≤ ± 2% of measured value |
Linearity |
≤ ± 1% of measured value + 0.1% of measurement range end |
Repeatability |
≤ ± 0.25% of measured value |
Materials |
Housing, cover, nut |
PPA |
Screws, seal, cable gland |
Sensor: stainless steel, EPDM, PA |
Parts in contact with
medium |
Sensor: stainless steel 1.4404/316L, FKM, PEEK
Fitting: see data sheet 406090 |
Electrical data |
Power supply voltage |
DC 18 to 36 V, reverse polarity protected |
Power consumption |
≤ 220 mA |
Output |
Current: 4 to 20 mA, three wires
Loop resistance: max. 1100 Ω at 36 V DC or max. 330 Ω at 18 V DC
Frequency pulse: 0 to 240 Hz
Clock ratio: 50%, ≤ 100 mA, protected against short circuit and reverse polarity
Relay: 3 A, 250 VAC, changeover contact
Alarm: when exceeding scale value: 22 mA or 256 Hz
Device error: 22 mA or 0 Hz |
Cable gland |
M20 x 1.5 |
Series terminals |
for lines with cross-section up to 0.75 mm2 |