Thông số kỹ thuật:  
Measurement of protective earth conductor resistance I=200mA 
(protection class I)
    
        
            | Display range | Resolution | Accuracy | 
        
            | 0,00...0,99Ω | 0,01Ω | ±(4% m.v. + 2 digits) | 
        
            | 1,00...19,99Ω | ±(4% m.v. + 3 digits) | 
    
 
• test current: ≥200mA for R= 0,2...1,99Ω
• upper limit adjustable in the 10mΩ …1,99Ω range with the 0,01Ω resolution
• measurement time adjustable in 1...60s range, with the 1s resolution
Measurement of protective earth conductor resistance I=10A 
(protection class I)
    
        
            | Display range | Resolution | Accuracy | 
        
            | 0...999mΩ | 1mΩ | ±(3% m.v. + 4 digits) | 
        
            | 1,00...1,99Ω | 0,01Ω | 
    
 
• technical method
• test current: ≥10A for R≤0,5Ω
• limit adjustable in the 10mΩ …1,99Ω range with the 0,01Ω resolution
• measurement time adjustable in 1...60s range, with the 1s resolution
Measurement of protective earth conductor resistance I=25A 
(protection class I)
    
        
            | Display range | Resolution | Accuracy | 
        
            | 0...999mΩ | 1mΩ | ±(3% m.v. + 4 digits) | 
        
            | 1,00...1,99Ω | 0,01Ω | 
    
 
• technical method
• measurement with sinusoidal current of the mains frequency, test current: ≥25A for R≤0,2Ω
• limit adjustable in the 10mΩ …1,99Ω range with the 0,01Ω resolution
• measurement time adjustable in 1...60s range, with the 1s resolution
Measurement of L-N circuit resistance 
    
        
            | Display range | Resolution | Accuracy | 
        
            | 0...999mΩ | 1mΩ | ±(5% m.v. + 5 digits) | 
        
            | 1,00...4,99Ω | 0,01Ω | 
    
 
• test voltage: 4...8V AC
• short-circuit current: max. 5mA
Measurement of insulation resistance
Measurement range according to IEC 61557-2 for:
UN=100V: 100kΩ...99,9MΩ 
UN=250V: 250kΩ...199,9MΩ 
UN=500V: 500kΩ...599,9MΩ
    
        
            | UN | Display range | Resolution | Accuracy | 
        
            | 100V | 0...1999kΩ | 1kΩ | ±(5% m.v. + 8 digits) | 
        
            | 2,0...19,99MΩ | 0,01MΩ | 
        
            | 20,0...99,9MΩ | 0,1MΩ | 
        
            | 250V | 0...1999kΩ | 1kΩ | 
        
            | 2,00...19,99MΩ | 0,01MΩ | 
        
            | 20,0...199,9MΩ | 0,1MΩ | 
        
            | 500V | 0...1999kΩ | 1kΩ | 
        
            | 2...19,99MΩ | 0,01MΩ | 
        
            | 20,0...599,9MΩ | 0,1MΩ | 
    
 
• limit adjustable in the: 0.01...9.9mA range with the 0.1MΩ resolution
• adjustable measurement time: continuous measurement (Cont), or from 4s to 3min with 1s resolution
• automatic discharge of the capacity of the tested device after measurement
• protection against measuring live devices 
• output current max. 1.4mA
Measurement of PE and residual leakage current:
    
        
            | Display range | Resolution | Accuracy | 
        
            | 0,00...3,99mA | 0,01mA | ±(5% m.v. + 2 digits) | 
        
            | 4,0...19,9mA | 0,1mA | 
    
 
• limit adjustable in the 0.01...9.9mA range with the 0.01mA/0.1mA resolution
• adjustable measurement time: continuous measurement (Cont), or 1...60s with 1s resolution
• in the middle of the measurement time, the meter automatically switches the polarity at the measuring terminal and displays the greater value
Measurement of equivalent leakage current:
    
        
            | Display range | Resolution | Accuracy | 
        
            | 0,00...3,99mA | 0,01mA | ±(5% m.v. + 2 digits) | 
        
            | 4,0...19,9mA | 0,1mA | 
    
 
• limit adjustable in the 0.01...9.9mA range with the 0.01mA/0.1mA resolution
• adjustable measurement time: continuous measurement (Cont), or 1...60s with 1s resolution
• open circuit voltage 25...50V
Measurement of touch leakage current:
    
        
            | Display range | Resolution | Accuracy | 
        
            | 0,00...4,999mA | 0,001mA | ±(5% m.v. + 3 digits) | 
    
 
• limit adjustable in the 0.01...9.9mA range with the 0.01mA/0.1mA resolution
• adjustable measurement time: continuous measurement (Cont), or 1...60s with 1s resolution
• current measurement band 20Hz...100kHz 
Measurement of power S:
    
        
            | Display range | Resolution | Accuracy | 
        
            | 0...999VA | 1VA | ±(5% m.v. + 3 digits) | 
        
            | 1...3,99kVA | 0,01kVA | 
    
 
• adjustable measurement time: continuous measurement (Cont), or 1...60s with 1s resolution
Measurement of current consumption:
    
        
            | Display range | Resolution | Accuracy | 
        
            | 0,00...15,99A | 0,01A | ±(2% m.v. + 3 digits) | 
    
 
• adjustable measurement time: continuous measurement (Cont), or 1...60s with 1s resolution
Voltage measurement:
    
        
            | Display range | Resolution | Accuracy | 
        
            | 187,0…265,0V | 0,01V | ±(2% m.v. + 2 digits) | 
    
Thiết bị đo cài đặt điện đa chức năng_ SONEL _ MPI-505