Technical data |
KPG 54kV VLF |
Power supply |
230 V (± 10%), 10 A, 50/60 Hz |
Output voltage |
0...57 kVrms VLF 0.1 Hz (0.05 Hz + 0.02 Hz optional)
± 0...62 kV DC |
Voltage waveshapes |
VLF: similar sine-wave, symmetrical, with true R.M.S. measurement
DC: direct voltage, negative and positive polarity |
max. load (VLF) |
4.4 µF / 18 kVrms , 0.1 Hz (app. 12.2 km) *C' = 0,36 µF/km
2.4 µF / 36 kVrms , 0.1 Hz (app. 9.6 km) *C' = 0,25 µF/km
0.9 µF / 54 kVrms , 0.1 Hz (app. 4.7 km) *C' = 0,19 µF/km
0.55 µF / 57 kVrms , 0.1 Hz (app. 2.9 km) *C' = 0,19 µF/km |
Overcurrent trip (DC) |
10 mA |
Discharge |
integrated automatic discharge device, max. 12500 J |
Voltage measuring range
|
-70...0...70 kV, accuracy 1%
|
Current measuring ranges |
± 0...100 µA / 1 mA / 10 mA |
Operating temperature |
-20 ... +45°C |
Duty |
Continuous operation |
PC interface
|
USB flash drive
|
Construction
|
in two parts, Operation unit and High Voltage unit |
Weight
Operation unit
HV unit |
17 kg
49 kg |
Dimensions (W x H x D)
Operation unit
HV unit |
37 x 34 x 20 cm
40 x 44 x 24 cm |