The portable cable test set
KPG 24kV VLF is used for testing of medium voltage cables in accordance to the standards IEC 60502-2, CENELEC HD 620 & 621, DIN VDE 0276/620 & 621 and IEEE 400.
Test is carried out with a low strain practice with VLF (very low frequency) test voltage of preferably 0.1Hz.
VLF testing enables detection of damages of insulation within shortest test time.
Thông số kỹ thuật
| Technical data |
KPG 24kV VLF |
| Power supply |
230 V (± 10%), 10 A, 50/60 Hz |
| Output voltage |
5...24 kVrms (34 kVpeak), 0.1 Hz VLF (0.05 + 0.02Hz optional)
± 0...34 kV DC |
| Voltage waveshapes |
VLF: similar sine-wave, symmetrical, with true R.M.S. measurement
DC: direct voltage, negative and positive polarity |
| max. load (VLF) |
5.0 µF at 24 kVrms , 0.1 Hz (app. 20 km)*
15 µF at 24 kVrms , 0.02 Hz (app. 60 km)*
6.8 µF at 18 kVrms , 0.1 Hz (app. 27 km)*
*at a cable capacitance of 0.25 μF/km
|
| Overcurrent trip (DC) |
10 mA |
| Discharge |
integrated automatic discharge device, max 9000 J
|
| Voltage measuring range |
-40 ... 0 ... 40 kV, accuracy 1%
|
| Current measuring ranges |
± 0 ... 100 µA / 1 mA / 10 mA |
| Operating temperature |
-20 ... +45°C |
| Duty |
Continuous operation |
| PC interface |
USB flash drive |
| Construction |
in two parts, Operation unit and High Voltage unit |
Weight
Operation unit
HV unit |
17 kg
38 kg |
Dimensions (W x H x D)
Operation unit
HV unit |
37 x 34 x 20 cm
40 x 41 x 24 cm |
>>> KPG 36kV VLF giá tốt