Sensor |
Housing |
Stainless steel 1.4571 |
|
Protection category |
IP 65, DustEx 20 or GasEx (option) |
|
Operating temperature |
Front end of sensor: - 20 … + 80 °C [-4 ... +176 °F]
Optional: - 20 … + 200 °C [-4 ... +392 °F]
Sensor electronic: 0 ... 60 °C [+32 ... +140 °F] |
|
Max. working pressure |
1 bar, optional 10 bar |
|
Working frequency |
K-Band 24,125 GHz (± 100 MHz) |
|
Transmitting power |
Max. 5 mW |
|
Weight |
1.3 kg |
|
Dimension |
Ø 60, Ø 20, L 271 mm |
|
Accuracy |
± 2... 5 % in calibrated range |
|
|
|
Transmitter |
Power supply |
110/230 V, 50 Hz (optional 24 V DC) |
|
Power consumption |
20 W / 24 VA |
|
Current consumption |
Max. 1 A at 24 V |
|
Protection category |
IP 65 according to EN 60 529/10.91 |
|
Operating temperature |
-10 ... + 45 °C [+14 ... +113 °F] |
|
Enclosure dimensions |
258 x 237 x 174 (W x H x D) |
|
Weight |
Approx. 2.5 kg |
|
Interface |
RS 485 / RS 232 C (ModBus) |
|
Cable glands |
3 x M16 (4.5 - 10 mm Ø) |
|
Screw terminals |
0.2 - 2.5 mm² [AWG 24 - 14] |
|
Current output signal |
4... 20 mA (0... 20 mA), load < 500 Ω |
|
Measurement value alarm relay output |
Relay with switching contact, max. 250 V AC, 1 A |
|
Data storage |
Flash |
|
Pulse output |
Open Collector - Max. 30 V, 20 mA |
|
|
|
C-Box |
Size |
98 x 64 x 35 mm (W x H x D) |