Working Condition
|
Temperature:5℃~40℃
|
Relative humidity:<80%(25℃时)
|
Altitude:<2500m
|
Power Frequency:50Hz±0.5Hz
|
Power Voltage:220V±5V
|
Measuring range
|
In-phase component (%):0.0001~200.0
|
Resolution:0.0001
|
Orthogonal Component (min): 0.001~700.0
|
Resolution:0.001
|
Impedance (Ω):0.0001~20.0
|
Resolution:0.0001
|
Admittance (ms):0.0001~20.0
|
Resolution:0.0001
|
Basic Error
|
In-phase Component
|
ΔX=±(X×2%+Y×2%)±Dx (with Class 1 to spare)
|
Orthogonal Component
|
ΔY=±(X×2%+Y×2%×34.48)±Dy (with Class 1 to spare)
|
“X”, “Y”——Values displayed
|
“Dx, Dy”——Quantization error
|
Dx=2,Dy=5
|
Percentage
|
Class 2 (with Class 1 to spare)
|
Working Range
|
Current
|
(1%~149%)In (In =5A)
|
(5%~149%)In (In =1A)
|
Voltage
|
(5%~149%)Un (Un =100V,150V,100V/)
|
(5%~149%)Un (Un =100V/3)
|
Working Load
|
Current
|
TO对TX<0.12Ω cosΦ=1
|
Voltage
|
a对x<0.25VA (100V)
|
Reversed Polarity Indication
|
Take action according to the polar instructions when the current is larger than 5% of the rated value and the error is larger than 180%.
|
Note: If no indication comes up when the current is larger than 10% of the rated value, malfunction exists. In that case please be sure not to increase the current so as not to burn the machine.
|
Indication of False Transformation Ratio
|
There should be an indication of false transformation ratio when the current is larger than 5% of the rated value and the error is between 30% and 180%.
|
Insulation and High Voltage Test
|
Terminal TX is connected with terminal ().
|
The power socket can bear a voltage of 1.5kV with respect to the outer shell for 1 min.
|