| Measuring values | 
            temperature | 
        
        
            | Output voltage | 
            TRV: 1x 0..10 V, min. load 5 kΩ | 
        
        
            | Output ampere | 
            TRA: 1x 4..20 mA, max. load 700 Ω | 
        
        
            | Output passive | 
            depending on used sensor | 
        
        
            | Network technology | 
            BACnet MS/TP, KNX (TP), LON FT (free topology), RS485 Modbus | 
        
        
            | Power supply | 
            15..24 V = (±10%) or 24 V ~ (±10%) SELV, TRA: 15..24 V = (±10%) SELV, KNX: supply via BUS | 
        
        
            | Power consumption | 
            TRV: typ. 0,4 W (24 V =) | 0,8 VA (24 V ~), TRA: typ. 0,5 W (24 V =), BACnet: typ. 0,4 W (24 V =) | 0,6 VA (24 V ~), KNX: 0,6 W (24 V =) | 1,2 VA (24 V ~), LON: typ. 0,5 W (24 V =) | 1,7 VA (24 V ~), RS485 Modbus: typ. 0,4 W (24 V =) | 0,6 VA (24 V ~), LCD TRV: typ. 0,6 W (24 V =) | 1,0 VA (24 V ~), LCD LON: typ. 0,85 W (24 V =) | 2,0 VA (24 V ~), LCD RS485 Modbus: typ. 0,4 W (24 V =) | 0,6 VA (24 V ~) | 
        
        
            | Measuring range temp. | 
            TRV | TRA: adjustable at the transducer, TRV1 | TRA1: -50..+50 °C, TRV3 | TRA3: 0..+50 °C, TRV8 | TRA8: -15..+35 °C, BUS: 0..+50 °C, passive: -35..+70 °C | 
        
        
            | Accuracy temperature | 
            ±1% of measuring range (typ. at 21 °C), passive: ±0,3 K (typ. at 21 °C), depending on used sensor | 
        
        
            | Sensor | 
            passive: 2-wire (standard), 3-wire or 4-wire | 
        
        
            | Display | 
            LCD 29x12 mm, monochrome, (optional) | 
        
        
            | Enclosure | 
            PC, pure white | 
        
        
            | Protection | 
            IP30 according to EN 60529 | 
        
        
            | Cable entry | 
            breaking points top/bottom, rear entry | 
        
        
            | Connection electrical | 
            terminal block, max. 1,5 mm² | 
        
        
            | Ambient condition | 
            -35..+70 °C, max. 85% rH non-condensing | 
        
        
            | Mounting | 
            surface mounted on flush-mounting box (Ø=55 mm) | 
        
        
            | Notes | 
            special painting available on request, for other sensors please request, multi-conductor connection on request, enclosure stainless steel available (see options) |