Measuring values |
temperature |
Output voltage |
2x 0..10 V, temperature, actuating variable valve drive |
Output switch contact |
Fan: floating contact NO, 250 V ~ / 6 A, Alarm: floating contact NO, 30 V ~ / 1 A |
Power supply |
15..24 V = (±10%) or 24 V ~ (±10%) SELV |
Power consumption |
max. 2 VA (24 V ~) |
Measuring range temp. |
-10..+120 °C |
Accuracy temperature |
±1 K (typ. at 0 °C) |
Inputs |
for passive sensor NTC10K (default), PT1000, Ni1000, Ni1000TK5000, adjustable, for external controller defining control value for valve, for fan (floating contact) |
Functions |
frost protection function, controlling valve actuator, alarm |
Display |
LED green – indicator valve actuator, LED red – alarm, LED yellow – fan |
Enclosure |
ABS, white |
Protection |
IP20 according to EN 60529 |
Connection electrical |
removable plug-in terminal, max. 2,5 mm² |
Ambient condition |
-40..+70 °C, max. 85% rH non-condensing |
Mounting |
prepared for mounting on DIN rail TS35 (35x7,5 mm) according to EN 60715 |