| Measuring values | 
            temperature | 
        
        
            | Medium | 
            gases, fluids | 
        
        
            | Output voltage | 
            TRV: 1x 0..10 V | 
        
        
            | Output ampere | 
            TRA: 1x 4..20 mA | 
        
        
            | Output passive | 
            depending on used sensor | 
        
        
            | Power supply | 
            TRV: 15..24 V = (±10%) or 24 V ~ (±10%) SELV, TRA: 15..24 V = (±10%) SELV | 
        
        
            | Power consumption | 
            TRV: typ. 1 W (24 V =) | 1,4 VA (24 V ~), TRA: typ. 0,5 W (24 V =) | 
        
        
            | Measuring range temp. | 
            TRV1 | TRA1: -50..+50 °C, TRV2 | TRA2: -10..+120 °C, TRV3 | TRA3: 0..+50 °C, TRV4 | TRA4: 0..+160 °C, TRV5 | TRA5: 0..+300 °C, passive: -50..+120|+150|+160|+260 °C, depending on used sensor | 
        
        
            | Accuracy temperature | 
            TRV | TRA: ±0,2 °C | ±0,1% of measured value (typ. at 21 °C), passive: ±0,3 K (typ. at 21 °C), depending on used sensor | 
        
        
            | Sensor | 
            passive: 2-wire (standard), 3-wire or 4-wire | 
        
        
            | Enclosure | 
            shape B, aluminium | 
        
        
            | Protection | 
            IP66 according to EN 60529, SI-Protection | 
        
        
            | Cable entry | 
            M20 for wire max. Ø=8 mm | 
        
        
            | Connection electrical | 
            terminal block, max. 1,5 mm² | 
        
        
            | Neck pipe | 
            stainless steel V2A, Ø=15 mm, L=70 mm | 
        
        
            | Pocket | 
            stainless steel V4A, Ø=8 mm, thread G 1/2", mounting length: 100 | 150 | 200 | 250 mm | 
        
        
            | Ambient condition | 
            -50..+160 | +150 | +120 °C (only end of senor), optional -80..+260 °C (only end of sensor), enclosure passive: -25..+90 °C, max. 85% rH short term condensation, enclosure TRV/TRA: -25..+70 °C, max. 85% rH short term condensation | 
        
        
            | Notes | 
            for other sensors please request |