| Measuring values |
temperature |
| Output voltage |
TRV: 1x 0..10 V, min. load 5 kΩ |
| Output ampere |
TRA: 1x 4..20 mA, max. load 500 Ω |
| Output passive |
depending on used sensor |
| Power supply |
TRV: 15..24 V = (±10%) or 24 V ~ (±10%) SELV, TRA: 15..24 V = (±10%) SELV |
| Power consumption |
TRV: typ. 0,4 W (24 V =) | 0,8 VA (24 V ~), TRA: typ. 0,5 W (24 V =) |
| Measuring range temp. |
TRV3 | TRA3: 0..+50 °C, passive: depending on used sensor |
| Accuracy temperature |
TRV | TRA: ±0,5 K (typ. at 21 °C within default measuring range), passive: ±0,3 K (typ. at 21 °C), depending on used sensor |
| Sensor |
passive: 2-wire (standard), 3-wire or 4-wire |
| Enclosure |
enclosure USE-S, PC, pure white, with removable cable entry, (only active) |
| Protection |
IP65 according to EN 60529 |
| Cable entry |
M16 for wire max. Ø=8 mm, removable, (only active) |
| Connection electrical |
removable plug-in terminal, max. 2,5 mm², (only active), connection wire PVC, 2x Ø=0,25 mm², grey, sensor wire active silicone, Ø=25 mm, 1 m (default), 2 m, 4 m, 6 m, for other lengths please request |
| Pocket |
aluminium, dimensions: 35x10x6 mm |
| Ambient condition |
-35..+70 °C, max. 85% rH short term condensation |
| Weight |
passive: 20 g, TRV/TRA: 115 g |
| Mounting |
surface mounting with adhesive strip (included), screw mounted possible using version with bore hole |
| Delivery contents |
incl. mounting base enclosure USE-S pure white |
| Notes |