Measuring values |
temperature |
Output voltage |
TRV: 1x 0..10 V or 0..5 V, LCD/relay: 0..10 V or 0..5 V (live-zero can be configured via Thermokon USEapp) |
Output ampere |
TRA: 1x 4..20 mA |
Output passive |
depending on used sensor |
Output switch contact |
Relay: 2x floating contact NO for 24 V ~ or 24 V = / 3 A |
Network technology |
LON FT (free topology), RS485 Modbus |
Power supply |
15..24 V = (±10%) or 24 V ~ (±10%) SELV, TRA: 15..24 V = (±10%) SELV, LON: 15..24 V = (±10%) or 24 V ~ (±10%) SELV, LCD/relay/BUS: 15..35 V = or 19..29 V ~ SELV |
Power consumption |
TRV: typ. 0,4 W (24 V =) | 0,8 VA (24 V ~), TRA: max. 0,5 W (24 V =), LON: typ. 0,5 W (24 V =) | 1,7 VA (24 V ~), LCD/relay/BUS: max. 2,5 W (24 V =) | 4,3 VA (24 V ~) |
Measuring range temp. |
-50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, TRV | TRA: adjustable at the transducer, default setting: -50..+50 °C, LON: -45..+130 °C, LCD/relay/RS485 Modbus: can be configured via Thermokon USEapp, default setting: -20..+80 °C, passive: depending on used sensor |
Accuracy temperature |
±0,5 K (typ. at 21 °C within default measuring range), passive: ±0,3 K (typ. at 21 °C), depending on used sensor |
Sensor |
2-wire (standard), 3-wire or 4-wire |
Display |
LCD 29x35 mm with RGB backlight, (optional) |
Enclosure |
enclosure USE-S, LCD/relay/RS485 Modbus: enclosure USE-M, PC, pure white, LCD: cover PC, transparent, LON: PA6, pure white, with quick lock screws |
Protection |
IP65 according to EN 60529 |
Cable entry |
M16 for wire max. Ø=8 mm, LON: M20 for wire max. Ø=8 mm, seal insert for double cable entry for wire max Ø=6 mm, Relay: M20 for wire max. Ø=8 mm incl. seal insert for double cable entry for wire max Ø=6 mm, BUS: M25 with fourfold cable entry for wire with max. Ø=7 mm, removable (all types enclosure USE) |
Connection electrical |
removable plug-in terminal, max. 2,5 mm², LON: terminal block, max. 1,5 mm², BUS terminal: removable plug-in terminal, max. 1,5 mm² |
Pocket |
stainless steel V2A, Ø=6 mm, L=25 mm |
Ambient condition |
enclosure: -35..+70 °C, max. 85% rH short term condensation, enclosure passive: -35..+90 °C, max. 85% rH short term condensation |
Delivery contents |
incl. mounting base enclosure USE-S pure white, LCD/relay/BUS: incl. mounting base enclosure USE-M pure white |
Notes |
for other sensors please request |