| General specifications | Mounting method | Panel mount or portable type | 
        
            | Power supply voltage | 100–240 V AC, 50/60 Hz | 
        
            | Power consumption | Approx. 47 VA (at 240 V AC) | 
        
            | Terminal | M3 screw terminal (Open collector outputs are D-sub connectors.) | 
        
            | Input section | Number of inputs | 9 or 18 points | 
        
            | Measurement cycle | 100 ms | 
        
            | Input signal | Thermocouple (type B, R, S, K, E, J, T, N, W, L, U, or PN) RTD (Pt100)
 DC voltage (50 mV, 500 mV, or 5 V)
 DC current (with shunt resister)
 
 | 
        
            | Burnout function | Provided as standard for thermocouple or RTD input | 
        
            | Display unit | Display | 5.7" TFT color LCD (320 240 dots) with automatic display off function | 
        
            | Life of backlight | 50,000 hours | 
        
            | Display contents | Trend, bar graph, digital display, event summery, historical trend, parameter, parameter setting, group, analog meter, scale, total data 
 | 
        
            | Recording function | Storage medium | CompactFlash | 
        
            | Recording capacity | 2 GB max. | 
        
            | Data saving cycle | Links to refreshment cycle of the trend display | 
        
            | Trend data | Maximum and minimum values are saved. | 
        
            | Event data | Alarm data and message data are saved. | 
        
            | Data format | ASCII (readable by Excel) Binary (not readable by Excel)
 | 
        
            | Storage capacity | Approx. 1.5 years' worth at a display refresh cycle of 30 seconds (ASCII, 9 channels, 256 MB CompactFlash) | 
        
            | Memory consumption | Displayed in bar graph Recording stops when the memory is full.
 | 
        
            | Calculation function | 
 | Difference between channels, F value, integration, square root extraction | 
        
            | Alarm | Number of settings | Up to 4 alarms for each channel | 
        
            | Alarm type | High/low limits | 
        
            | Indication | Alarm status is displayed on digital display when an alarm occurs. Histories are displayed in the alarm summary.
 
 | 
        
            | Relay contact output | 10 points (option) *Not available for 18-inputs version. | 
        
            | Open collector output | 18 points (option) | 
        
            | Performance | Indication accuracy | ±(0.15% + 1 digit) of input range | 
        
            | Indication resolution | 0.1°C | 
        
            | Reference junction compensation error
 | ±0.5°C | 
        
            | Others | Memory backup | Parameter settings are saved to the internal nonvolatile memory. The clock is backed up by a built-in lithium battery.
 Trend data is stored in CompactFlash with no back-up.
 
 | 
        
            | Option | Alarm output/DI | 10 relay outputs and 5 digital inputs (Not available for 18-inputs version.), or 18 open collector outputs and 5 digital inputs are added.
 | 
        
            | Communication | Ethernet or RS485 (MODBUS) interface with 18 alarm (open collector) outputs and 5 digital inputs | 
        
            | Accessories | Panel mount type | Data viewer software, parameter loader software, panel mounting bracket, noise filter for power cable, front panel packing, instruction manual (CD-R) 
 | 
        
            | Portable type | Data viewer software, parameter loader software, power cable (2 m), noise filter for power cable, instruction manual (CD-R) |