| Power supply voltage | 100–240 V AC, 50/60 Hz | 
        
            | Power consumption | ≤ 5 VA (at 100 V) or ≤ 6 VA (at 220 V) | 
        
            | Input | RTD (Pt100), thermocouples (9 types) | 
        
            | Indication accuracy | (±0.5% of indicated value or 1°C, whichever is larger) ±1 digit ±1°C | 
        
            | Sampling rate | 0.2 s | 
        
            | SV/PV correction | Provided | 
        
            | Control | ON/OFF control, PID control (with auto-tuning), Fuzzy control | 
        
            | Control output | Relay contact output or SSR/SSC driving output | 
        
            | Alarm output | 1 or 2 (option) | 
        
            | Alarm type | absolute value, deviation value, zone, high, low, hold, alarm latch, excitation/non-excitation | 
        
            | Burnout | If burnout occurs, the output goes to high limit or low limit. | 
        
            | Display | 7-segment 4-digit LED Process value and set value
 | 
        
            | Parameter loader software | 
                Allows parameter setting, editing, and savingNo need for power supply for PXEYou cannot control temperature via the software | 
        
            | Enclosure | IP66, NEMA-4X equivalent (when mounted on panel), with front waterproof packing | 
        
            | Dimensions and weight | 48 (W) × 48 (H) × 63.5 (D) mm, approx. 100 g | 
        
            | Mounting | Panel mount (mounting fixture provided) | 
        
            | Terminal | M3 screw terminal | 
        
            | Ambient temperature | -10°C to +50℃ | 
        
            | Approval | CE marking, RoHS |