General ETL-35 specifications:
Characteristic |
Value |
Single-phase AC power supply voltage, V
|
220±22
|
Power supply frequency, Hz
|
50±2 |
Consumed current, A, max
|
80 |
Net weight, kg, max |
700 |
Operating personnel, people, min |
2 |
Lifespan, years, min |
10 |
High voltage tester BVI based on the current transformer IOM-100/16specifications:
The unit is intended for testing the insulation of power cables and solid dielectric with the rectified voltage of up to 60 kV, as well as for testing solid dielectrics with sinusoidal voltage of up to 100 kV (RMS) at 50 Hz.
Characteristic |
Value |
Maximum rectified voltage under continuous running duty, kV
|
60 |
Maximum running current under rectified voltage, mA |
100 |
Maximum AC voltage (RMS), kV |
100 |
Maximum operating current under AC voltage (RMS), mA
|
100 |
Dimensions, mm, max |
650x84
|
Net weight, kg, max |
220 |
Dissipation factor meter IDP-10 specifications:
IDP-10 measures a capacity and dissipation factor of objects at the AC voltage of 10 kV at 50 Hz within the limits established by the AC bridge SA-7100/2.
Characteristic |
Value |
Maximum AC voltage (RMS), kV
|
10 |
Reduced AC voltage measurement error, %, max
|
3 |
Dimensions, mm, max |
220х300х350 |
Net weight, kg, max |
5 |
High potential DC current meter ITVC-20 specifications:
ITVC-20 is designed for measuring the DC current of the negative polarity in the circuits with the potential of up to 60 kV with respect to the ground.
Characteristic |
Value |
Measurements range, mA
|
0.1 ... 20
|
Maximum relative measurement error in a given range
|
3 |
Maximum multiplication factor of the microammeter overloading
|
3.5 |
Maximum allowed potential of device casing with respect to the ground, kV |
60 |
Voltage drop between the device's terminals, V
|
2
|
Dimensions, mm, max |
165х100 |
Net weight, kg, max |