Number of Measuring Circuit |
16 circuits (channels) |
Detection Method |
Clamp-on CT method |
Measuring Range |
DC 0~99.9A |
Minimum Resolution |
0.1A |
Measuring Accuracy |
±3%rdg±5dgt |
Sampling |
Approx. 20mS |
Measuring Temperature |
0~50℃, less than 80%RH w/o condensing |
Measuring Circuit Voltage |
less than DC600V (insulated conductor) |
Withstanding Voltage |
AC2200V (50 / 60Hz) one minute between power supply source and housing case |
Power Supply |
AC100V~240V with adapter
Internal Ni-hydride Battery
|
Battery Life |
Approx. 4 days at continuous use by full charge |
Dimensions & Weight |
236(W) x 170(H) x 56(D)mm, approx. 840gs |
Standard Accessories |
Carrying Case, AC Adapter, USB Cable, Instruction Manual |
Optional Accessories |
Clamp CT with i.d. 30mm & 2.8m cable, CT Carrying Case (for max. 8 CTs) |