Measurement Accuracy: |
|
Real Power and Energy: |
IEC 62053-22 Class 0.5S, ANSI C12.20 0.5% |
Reactive Power and Energy: |
IEC 62053-23 Class 2, 2% |
Current: |
0.4% (+0.015% per °C deviation from 25°C) from 5% to 100% of range;
0.8% (+0.015% per °C deviation from 25°C) from 1% to 5% of range |
Voltage: |
0.4% (+0.015% per °C deviation from 25°C) from 90V (L-N) to 600VAC (LL) |
Sample Rate: |
2520 samples per second |
Data Update Rate: |
1 sec |
Type of Measurements: |
True RMS up to the 21st harmonic 60 Hz, One to three phase AC system |
Input Voltage Characteristics: |
|
Measured AC Voltage: |
Minimum 90VL-N (156VL-L) for stated accuracy
UL Maximums: 600VL-L (347VL-N)
CE Maximums: 300VL-N (520V L-L) |
Metering Over Range: |
+20% |
Impedance: |
2.5 MΩ (L-N)/5 MΩ (L-L) |
Frequency Range: |
45 to 65 Hz |
Input Current Characteristics: |
|
CT Scaling: |
Primary: Adjustable from 5 A to 32,000 A |
Measurement Input Range: |
0 to 0.333VAC or 0 to 1.0VAC (+20% over-range) |
Impedance: |
10.6kΩ (1/3 V mode) or 32.1kΩ (1 V mode) |
Output: |
|
Alarm Contacts: |
N.C., static output (30VAC/DC, 100mA max. @ 25°C, derate 0.56mA per °C above 25°C) |
Real/Reactive Energy
Pulse Contacts: |
N.O., static output (30VAC/DC, 100mA max. @ 25°C,
derate 0.56mA per °C above 25°C) |
Mechanical Characteristics: |
|
Weight: |
0.62 lb (0.28 kg) |
IP Degree of Protection (IEC 60529): |
IP40 front display; IP20 Meter |
Display Characteristics: |
Back-lit blue LCD |
Terminal Block Screw Torque: |
0.37 ft•lb (0.5 N•m) nominal/0.44 ft-lb (0.6 N•m) max |
Terminal Block Wire Size: |
26 to 14 AWG (0.13 to 2.08 mm2) |
Rail: |
T35 (35mm) DIN Rail per EN50022 |