AXF16- 1280v.2
|
AXF25- 1563v.2
|
AXF28- 1960v.4
|
AXF25- 3126v.4
|
Voltage (adjusted with knob)
|
0-8kV; 0-16kV
|
0-12.5kV; 0-25kV
|
0-14kV; 0-28kV
|
0-12.5kV; 0-25kV
|
Thump Rate
|
Approx. every 10-15 Seconds
|
Energy
|
1280 Joules @ 8kV and 16kV
|
1563 Joules @ 12.5kV and 25kV
|
1960 Joules @ 14kV and 28kV
|
3126 Joules @ 12.5kV and 25kV
|
Burner
|
Optional
|
150mA
|
Weather
|
Operation from -25º F (-31º C) to 110º F (43º C). Unit & Controls sealed for all weather operation.
|
Controls
|
All controls are motorized and operated by toggle switches.
|
12V Internal Battery
|
Standard
|
|
120V AC
|
Standard
|
12V DC External
|
Standard
|
|
240V AC
|
Optional
|
Dimensions
|
48” (1.2m) Height, 29.5” (75cm) Wide
|
Weight
|
230 Lbs. (105kg)
|
250 Lbs (114kg)
|
250 Lbs (114kg)
|
340 Lbs. (154kg)
|
Leads
|
50’ (15.25m) Shielded HV Lead terminated in Male MC Connector and a 15’ (4.5m) #2 Ground Cable are standard. Cable Reel Systems, EPR-X-ray Cable HV Leads and Custom Lengths are also Available.
|
HV Coupler/Filter
|
An inductive filter is used to minimize distortion and energy loss.
|
TDR Specifications
|
v.2 Monochrome
|
v.4 Color
|
Auto Analyze
|
Automatically marks end of cable and fault location and gives distance.
|
Screen
|
3.5” (8.9cm) x 4.5” (11.4cm) LCD (320x240) – Backlight Visible in Bright Light
|
10.5" diagonal (243mm x 185.1mm) color TFT LCD – Backlight Visible in Sun Light
|
Environmental
|
Radar contained within the sealed case of the thumper allowing all weather operation. Operable from -25ºF (-31ºC) to 110ºF (43ºC).
|
Radar contained within the sealed case of the thumper allowing all weather operation. Operable from 20ºF (-7ºC) to 120ºF (49ºC).
|
Accuracy
|
0.5% of the range selected
|
Memory
|
9 Memories available. Software is also available for downloading traces to a Laptop
|
15 Memories available. Software is also available for downloading traces to a Laptop
|
Additional Features
|
3 phase display, Current Impulse Method (CIM) available as options
|