Type
|
500 Ampere current source
|
Physical specifications
|
16”W x 14”H x 13” D (40.6 cm x 35.5 cm x 33 cm). Weight: 93 lbs. (42.2 Kg)
|
Input power
|
100 - 120 Vac or 200 - 240 Vac (factory pre-set), 50/60 Hz
|
Output currents
|
500A @ 4V, 125A @ 14V, 25A @ 70V
|
Internal current meter
|
1 A - 3000A; accuracy: 1% of reading, ±2 digits
|
Measurement method
|
Isolated CT
|
Timer reading range
|
0.1ms - 2 hours (also displayed in cycles); accuracy: 0.1% of reading, ±0.1ms
|
Timer stop inputs
|
voltage input (20V - 300V, dc or peak ac), dry contact input, or removal of test current
|
Display
|
back-lit LCD screen (128 x 64 pixels); viewable in bright sunlight and low light levels
|
Safety
|
Designed to meet IEC61010 (1995), UL61010A-1, CSA-C22.2 standards
|
Environment
|
Operating: -10°C to +50°C (+15°F to +122°F); Storage: -30°C to +70°C (-22°F to +158°F)
|
Humidity
|
90% RH @ 40°C (104°F) non-condensing
|
Altitude
|
2000 m (6,562 ft) to full safety specifications
|
Cables
|
two 5-foot (1.5m) #2/0 current cables, two 8-foot (2.5m) external timer input cables with alligator clips, one ground cable, one power cord
|
Furnished accessories
|
Transportation case
|
Warranty
|
1 year on parts and labor
|