AE865C Specifications
|
Type
|
Mini Degasifier
|
Physical specifications
|
23" (585 mm) Wide x 23" (585 mm) Deep x 46" (1,170 mm) // 275 lbs. (125 kgs.)
|
Input power
|
120Vac/60Hz - 220Vac/50Hz - other available configuration (choose it in the order)
|
Strainer
|
One Strainer, complete with a 60 mesh basket.
|
Heater
|
One 3 KW Electric Inlet Oil Heater. The heater shall have a watt density not greater than 11 W/Sq. In. (1.7 W/cm2). The heater shall be capable of increasing the oil temperature 45ºF (27ºC) in a single pass. Fuses shall be used for over current protection of each bank of heater elements.
|
Temperature Controller
|
One Temperature Controller, which shall be used to control the electric heating elements to maintain the desired oil temperature. The controller shall be integrally mounted on the heating unit. The temperature controller, on deviation from the set point, activates the heater contactor which energizes the heating element, raising the oil temperature to the set point. The controller set point is adjustable by a dial, thereby changing the set point. The heater controller is designed to drop out the heating load on loss of power or vacuum. On resumption of power or flow, the controller resumes function and begins to energize the heating element as required.
|
Degasification Chamber
|
One Degasification Chamber. The chamber shall have a viewing port and a bolted service door.
|
Float Actuated Level Control Valve
|
One Float Actuated Level Control Valve. The valve is actuated by a float mechanism in the dehydration chamber to maintain the desired oil level. The level control valve is fully modulating and will maintain an inlet flow equal to the capacity of the discharge pump.
|
Vacuum Pump
|
One Rotary Vane Vacuum Pump, 6 CFM (10 m3/hr) capacity, blank off rating 0.02 mm Hg. Vacuum required for processing is created by the vacuum pump
|
Vacuum Gauge
|
One 0-40 mm Hg Vacuum Gauge to indicate the vacuum in the processing chamber
|
Vacuum Trap
|
One Vacuum Trap to protect the vacuum pump from water carry-over
|
Temperature Gauge
|
One Temperature Gauge, which is used to indicate the outlet temperature of the oil being processed.
|
Pressure Gauge
|
One Pressure Gauge, which is used to indicate the outlet oil pressure and filter condition.
|
Degasification Header
|
One Degasification Header, which shall contain chemically inert accelerator elements
|
High Level Detector
|
One (1) High Level Detector. This level switch shall stop the vacuum pump to prevent flooding and is a back-up for the flow control valve Float Actuated Level Control Valve
|
Low Level Switch
|
One (1) Low Level Switch shall be interlocked with the discharge pump to prevent it from operating unless sufficient oil head is present
|
Discharge Pump
|
One (1) Positive Displacement Discharge Pump, with mechanical seals and integral relief valve. The pump shall have a rating of 60 GPH (225 litres per hour) and shall be direct driven by a ¼ HP, 1200 RPM, TEFC electric motor.
|
Oil Filter
|
Oil Filter will be installed after the outlet pump. The Afterfilter is furnished with a micron selectivity of 0.5 microns and a filtration efficiency of 98%.
Standard filter units are of steel construction and complete with pressure gauge to monitor differential pressure.
|