Type
|
Load tap changer analyzer
|
Physical specifications
|
21”W x 17”H x 9” D (53 cm x 43 cm x 24 cm); Weight: 33 lbs (15.4 kg)
|
Operating voltage
|
100 - 240 Vac, 50/60 Hz
|
Resistance reading range
|
1 micro-ohm - 500 ohms
|
Accuracy
|
1 - 19,999 micro-ohms: ±0.5% reading, ±1 count;
20 - 999 milli-ohms: ±1% reading, ±1 count;
1 - 500 ohms: ±1.5% reading, ±1 count
|
Test current
|
1 ampere, 5 amperes, 10 amperes
|
Test voltage
|
60 Vdc max
|
Resistance channels
|
Three static resistance reading channels, One dynamic resistance channel
|
Ac current input
|
Clamp-on current sensor, 1 – 20 Amperes
|
Display
|
Back-lit LCD Screen (128 x 64 pixels); viewable in bright sunlight and low-light levels
|
Printer
|
Built-in 4.5-inch wide thermal printer
|
Internal data storage
|
Stores up to 128 static resistance test records (48 tests per record) and 11 dynamic resistance test records
|
External data storage
|
One USB Flash drive interface port; stores up to 999 test records on a USB Flash drive (not included)
|
Computer interface
|
One RS-232C port, one USB port
|
Load tap changer contact
|
Designed to meet IEC 61010 (1995), UL 61010-a, and CAS-C22.2 standards
|
Safety
|
Designed to meet UL 61010A-1 and CAN/CSA C22.2 No. 1010.1-92 standards
|
Environment
|
Operating: -10°C to +50°C (+15°F to +122°F); Storage: -30°C to +70°C (-22°F to +158°F)
|
Humidity
|
90% RH @ 40°C (104°F) non-condensing
|
Altitude
|
2,000 m (6,562 ft) to full safety specifications
|
Cables
|
One 50-foot current cable set, three 50-foot resistance cable sets, ground cable, USB cable, RS-232C cable, LTC cable, power cord, cable bag
|
Optional accessories
|
Transportation case
|
Warranty
|
1 year on parts and labor
|