- Extremely stable with low detection limit at 6 ppb
- Suitable for trace SF6 leak detection, with up to 24 channel multiplexing possible
- Capable of measuring up to 3x the maximum allowable concentration (MAC = 1000 ppm for SF6)
- System designed to minimize interference from vibration, and automatically compensate for temper-ature, pressure, and humidity interference.
Thông số kỹ thuật
Detection Principle |
Photoacoustic Infrared Spectroscopy |
Detection Limit |
6 ppb (standard) |
Response Time |
27s (Standard Mode); 13s (Fast Mode) |
Dynamic Range |
5 - 50,000 ppb (50 ppm) Standard; 1 - 4,000 ppm Optional |
Repeatability |
1% of Measured Value |
Zero Drift |
± Detection Limit per Quarter |
Influence of temperature |
±10% of Detection Limit per ˚C |
Influence of presure |
±0.5% of Detection Limit per mbar |
Range Drift |
±2.5% of Measured Value per Quarter |
Influence of temperature |
±0.3% of Measured Value per ˚C |
Influence of pressure |
-0.01% of Measured Value per mbar |