Type
|
Portable current transformer test set
|
Physical specifications
|
17"W x 12½"H x 12"D (42.7 cm x 32cm x 26.9 cm); Weight: 55 lbs (25 kg)
|
Input power
|
100 ¬ 120 Vac or 200 ¬ 240 Vac (factory pre-set), 50/60 Hz
|
Measurement method
|
ANSI/IEEE C57.12.90, IEC 60044-1 and ANSI/IEEE C57.13.1
|
Output test voltages
|
0 ¬ 50 Vac @ 10A max; 0 – 200 Vac @ 10A max; 0 – 1200 Vac @ 1.5A max (5 min on, 10 min off)
|
Voltage reading range
|
0 ¬ 1,250 Vac; Accuracy: ±1.0% of reading, ±0.5 volt
|
Current reading range
|
0 ¬ 10A; Accuracy: ±1.0% of reading, ±0.02A
|
Current ratio range
|
0.8 ¬ 99: ±0.5%, 100 ¬ 999: ±1.0%, 1,000 ¬ 5,000: ±2%
|
Phase angle measurement
|
0 - 360 degrees; Accuracy: ±1.0 degree
|
Resistance reading range
|
100 micro-ohms ¬ 10 ohms; Accuracy: 2% of reading, ±1 count, ±10 micro-ohm
|
Display
|
Back-lit LCD Screen (20 characters by 4 lines); viewable in bright sunlight and low-light levels
|
Printer
|
Built-in 4.5-inch wide thermal printer
|
Computer interfaces
|
One RS-232C port, one USB port
|
PC software
|
Windows®-based CT Analysis software is included with purchase price
|
Internal test record storage
|
Stores 128 test records. Each test record may contain up to 10 sets of excitation, resistance and ratio data
|
Internal test header storage
|
Stores 10 test header records
|
Safety
|
Designed to meet UL 6101A-1 and CAN/CSA C22.2 No 1010.1-92 standards
|
Environment
|
Operating: -10°C to +50°C (+15°F to +122°F); Storage: -30°C to +70°C (-22°F to +158°F)
|
Humidity
|
90% RH @ 40°C (104°F) non-condensing
|
Altitude
|
2,000 m (6,562 ft) to full safety specifications
|
Cables
|
One 20-foot X cable set, one 35-foot H cable set, power cord, one cable carrying duffel bag
|
Options
|
Transportation case
|
Warranty
|
One year on parts and labor
|