Rated Primary Current |
AC100A |
CT Inside Diameter |
φ31mm |
Applicable Frequency |
50/60Hz |
Output Characteristic(RL=530Ω) |
Primary Input Current 0.1A / Criterion Output 50mV / Tolerance +5%-10%
Primary Input Current 0.2A / Criterion Output 100mV / Tolerance +5%-10%
Primary Input Current 0.4A / Criterion Output 200mV / Tolerance +5%-10%
Primary Input Current 0.8A / Criterion Output 400mV / Tolerance +5%-10% |
Load Resisance |
530Ω |
Equilibrium Characteristic |
Less than 30mV(max. residual voltage when AC42mA is piled up to the rated current) |
Output Part |
M4 Terminal |
Applicable Circuit |
Single Phase/Three Phase |
Rated Voltage |
Less than AC600V for low voltage circuit of coated wires |
Withstanding Voltage |
AC2200V/1 minute (between output terminal and CT) |
Insulation Resistance |
More than 50MΩ by 500V insulation tester (between output terminal and CT) |
Operation Temperature |
-10~60℃, 45~80%RH w/o condensation |
Dimension |
130×100.5×34.7mm |
Weight |
Approx. 560g |
Standard |
Compliant with RoHS directive |