- The device can auto check if the wire was correctly connected, and display the vector diagram of three phase current, voltage when test the three phase transformer.
- Single machine can make the loading test for substation transformer under 1000KVA; can make the loading test with 1/3 of the rated current for substation transformer under 3150KVA (the device can convert to the loading losses parameters if the rated current under 1/3 of the rated current)
- All the related test results are automatically corrected. Instrument can automatically such as: the waveform correction, temperature correction, non-rated voltage correction, calibration, and other non-rated current correction, so that more accurate test results.
- Can accurately measure capacity of distribution transformer , convenient and accurate.
- Measure the transformer no-load current, no-load loss; short-circuit voltage, short circuit (load) loss, capacity.
- The device with auto switching range, allow measure wide range voltage and current, simple wiring;
- 320x240 LCD, friendly man-machine interface, brilliance control, adapts to all seasons.
- The device can be preset 40 groups parameters of testes objects, and these parameters can be deleted or added at any time as needed, easy to use.
- With electronic clock, auto record the data, time, it is good for saving and managing the test results.
- Panel type printer can print the test results on site.
- Data (specimen setting, test results, measurement time) can be saved on power failure and can be reviewed, it can store 500 groups test results, can connect with computers to transmit data.
- Allow external connecting CT and PT to make extension measurement, can test the specimen with any parameters.
Thông số kỹ thuật
1. Service conditions
|
Temperature
|
-5°C~40°C
|
Humidity
|
<95%(25°C)
|
Altitude
|
<2500m
|
Outside interference
|
no exceptionally strong vibration, no extra - strong electromagnetic fields.
|
Power supply
|
220VAC±10%,45Hz~55Hz.
|
2. Main technical parameters
|
Active parts:
|
Current output
|
0 ~ 10A
|
Voltage measurement
|
0 ~ 10V
|
Test Capacity
|
10KV oil-immersed, dry-type transformers: 30KVA ~ 2500KVA
|
35KV oil-immersed transformers: 50KVA ~ 31500KVA
|
20KV dry type transformers: 50KVA ~ 2500KVA
|
35KV dry type transformers: 50KVA ~ 2000KVA
|
Features parts:
|
Voltage
|
0~450V (phase voltage), 0 ~ 800V (line voltage), auto-switch the measurement range
|
Current
|
0 ~ 100A, auto-switch the measurement range
|
Frequency
|
45Hz ~ 65Hz
|
3. Test accuracy
|
Voltage
|
20 ~ 100V, ± 0.2% FS; 100 ~ 450V, ± 0.2%
|
Current
|
0.5 ~ 10A, ± 0.2% FS; 10 ~ 100A, ± 0.2%
|
Power
|
± 0.5% (CosΦ> 0.1), ± 1.0% (0.02 <CosΦ <0.1)
|
4. Dielectric strength
|
The insulation resistance between voltage, current input terminal and the chassis≥100MΩ.
|
Between power supply input terminal and the shell can withstand 2KV (rms), for 1 minute
|
5. Dimension
|
400×300×170mm
|
6. Weight
|
6kg (not including test lines)
|