| Parameter | Value | 
            
                | Supply voltage single-phase alternating current, V | 230 ± 23 | 
            
                | Frequency, Hz | 50 ± 2 | 
            
                | Maximum power consumption, kVA, max | 3 | 
            
                | Highest output voltage, kV: | 
            
                | - AC | 50 | 
            
                | - DC | 70 | 
            
                | Highest output current, mA: 
 | 
            
                | - on AC voltage 
 | 44 
 | 
            
                | - on DC voltage 
 | 14 
 | 
            
                | Reduced voltage error, %, max: | 
            
                | - AC voltage from 2 kV to 50 kV 
 | ± 3 | 
            
                | - DC voltage from 2 kV to 70 kV | ± 3 
 | 
            
                | Reduced current error, %, max: 
 | 
            
                | - AC from 1,0 mA to 45,0 mA 
 | ± 3 | 
            
                | - DC from 0,5 mA to 14,5 mA 
 | ± 3 
 | 
            
                | Maximum current threshold on the high-voltage side, mA, max: | 
            
                | - AC voltage | 45 | 
            
                | - DC voltage | 14.5 | 
            
                | Control Unit dimensions, mm, max | 349 × 256 × 240 
 | 
            
                | Control Unit Weight, kg, max | 14 | 
            
                | High Voltage Unit dimensions, mm, max | 360 × 500 × 310 | 
            
                | High Voltage Unit weight, kg, max | 35 | 
            
                | lifespan, years, avg | 10 |