| Standard housing with right angle plug: | material: st. steel mat.-no. 1.4301 (304) degree of protection: IP 65
 | 
        
            |  | Silicon cover plate for trimming potentiometers. Right angle plug as per DIN EN 175301-803-A (DIN 43650, form A) with cable gland M16x1.5 mm,
 cable diameter 4...10 mm.
 | 
        
            |  | Inner chamber aeration for measuring ranges ≤ 10 bar. | 
        
            | Field housing, solid design: | material: st. steel mat.-no. 1.4301 (304) degrees of protection | 
        
            |  | standard IP 65: - inner chamber aeration via integrated sintered´filte, only for excess pressure measuring ranges ≤ 10 bar, if aeration via cable is impossible.
 | 
        
            |  | option: IP 67, inner chamber aeration via connection cable for excess pressure measuring range ≤ 10 bar
 | 
        
            |  | Screwable cover ring with O-ring seal for the externally accessible trimming potentiometers Screwable case cap for connection chamber
 | 
        
            |  | Connection terminals 4 mm² | 
        
            |  | Cable gland M16x1.5 for cable diameter 4.5...10 mm, material polyamide | 
        
            | Process connection: | - G1/2 B, EN 837-1 - G1/2 B, flus mounted
 | 
        
            | Measuring system: | piezoresistive measuring bridge, protected by integrated stainless-steel diaphragm.Completely welded system | 
        
            | Filling material: | silicone-free, synthetic oil | 
        
            | Material: | diaphragm: st. steel mat.-no. 1.4404 (316L) socket: st. steel mat.-no. 1.4404 (316L)
 | 
        
            | Weights: | standard housing: approx. 300 g fiel housing: approx. 750 g
 | 
        
            | Storage temperature range: | -25...+80 °C | 
        
            | Limiting temperature range: | -25...+70 °C | 
        
            | Rated temperature range: | -10...+70 °C | 
        
            | Temperature influence: | on zero point and meas. span: ≤ 0.02 % of meas. span/K | 
        
            | Auxiliary power supply: | standard version: - nominal voltage 24 V DC
 - function range 2-wire technology 14...30 V DC
 - 3-wire technology 16...30 V DC
 - max.permiss.operating voltage 30 V DC
 | 
        
            |  | Ex design: permiss. voltage range of 2-wire circuitry 15...30 V DC | 
        
            |  | Ex design: permiss. voltage range of 3-wire circuitry 16...30 V DC | 
        
            | Overload limits UE: | for short-time overload. See order details | 
        
            | Overload influenc: | ≤ 0.1 % f.s. | 
        
            | Output signal: | 4...20 mA, 2-wire technology, standard.Further possibilities see order details | 
        
            | Test output (with field housing only: | non interruptible output current measurement via integrated LOC diode | 
        
            | Current limitation in output signall: | max. output current approx. 30 mA | 
        
            | Supply voltage influenc: | ≤ 0.2 % f.s. / 10 V | 
        
            | Linearity error incl. hysteresis: | ≤ 0.3 % f.s. (limit point calibration) | 
        
            | Adjustable range: | zero point and measuring span approx. ± 10 % | 
        
            | Response time: | ≤ 20 ms | 
        
            | Electrical data: | Sum of maximum values in the intrinsically safe circuits Ui = 30 V
 Ii = 100 mA
 Pi = 0,7 W
 | 
        
            |  | For more information see data sheet. | 
        
            | Caution: | Make sure that there is equipotential bonding along the entire wiring run both inside and outside the explosion hazardous area. | 
        
            |  | Switch off device if it is installed in zone 0 and in temperature class T5 and T6 and it fails! | 
        
            | Burden: | - current output 2-wire circuitry:
 | 
        
            |  | standard: Ra = UB-14 V / 20 mA (KOhm) Ex-protection: Ra = UB-15 V / 20 mA (KOhm)
 | 
        
            |  | - voltage output: a current of 20 mA can be obtained in the case of devices with power output.
 | 
        
            | Burden influence: | for 500 Ohm burden of change: ≤ 0.1 % f.s. | 
        
            | GL approval (German Lloyd): | per certificat no. 60208-09 HH | 
        
            | EMC-Test | - noise immunity as per EN 50082, section 2, March 95 issue for industry - emitted interference as per EN 50081, section 1, 1993 issue for residential and industrial areas
 |